Read Online or Download Ansi Std c37.60-1981 (Ieee Standard Requirements For Overhead, Pad Mounted, Dry Vault, And Submersible Automatic Circuit Reclosers And Fault Interrupters For Ac PDF

Similar technique books

Read e-book online Embedded Generation PDF

Call for for on-site and replacement strength iteration is growing to be, fueled by way of executive and public strain to extend new release from renewable assets and effort effective plant, and by means of the capability financial advantages as a result of privatization and deregulation of the provision zone. This ebook is a pragmatic, course-derived advisor that covers all facets of embedded (or dispersed) iteration, from best mover features to community reliability modelling.

Read e-book online Mastering Calculations in Linear and Nonlinear Mechanics PDF

Modeling and simulation are significant to a mechanical engineer's activity. Increasingly complicated versions are getting used normally on an everyday basis. This revolution is the results of the intense growth in computing device expertise when it comes to either and software program. This paintings offers with the regulate of the hypotheses top from a mechanical version, frequently coming from continuum mechanics, to a numerical version, i.

Extra resources for Ansi Std c37.60-1981 (Ieee Standard Requirements For Overhead, Pad Mounted, Dry Vault, And Submersible Automatic Circuit Reclosers And Fault Interrupters For Ac

Example text

If colors are used to indicate an open or closed position, red shall signify closed and green signify open, with the words OPEN or CLOSED in contrasting colors. 2 Grounding Provisions. A recloser with a metal housing shall have provisions for the connection of a ground lead. The ground connector shall accommodate a ground conductor of a size adequate to conduct the rated interrupting current of the recloser for a period of 3 s without damage t o the conductor or connector. Pad mounted, dry vault and submersible reclosers shall have an additional grounding connection for each three-phase set of cable entrances.

The above tests shall also be applied to a properly rated transformer, connected as shown in Fig 5(b). Fifteen positive and fifteen negative surges shall be applied. 3 Condition of Control During and After Test. The control shall not close the recloser from an open position during the application of surges. Tripping from a closed position is permissible on a reclosing switchgear device. Malfunction of the control t o cause lockout on one surge is not permissible. Following the tests, the recloser and control apparatus shall be capable of performing all normal functions without impairment.

10 Separate Mounting of Control Apparatus. Where applied, control apparatus shall be capable of being mounted separately from the recloser in normal service. 13 Vacuum Interrupters. 85-1972 Cl]. X-radiation generated shall not exceed the value in Table 1of that standard. 11 Counters. An operations counter shall be provided to indicate the total number of operations of the recloser. The counter shall be visible with the recloser in service.